Gas Insulated Switchgear 2500A from 11kV up to 36kV

FOB Reference Price:Get Latest Price
$5,000.00 - $10,000.00 / Sets | 1 Set/Sets (Min. Order)
Report Suspicious Activity
Overview
Quick Details
Place of Origin:
Zhejiang, China (Mainland)
Brand Name:
Rockwill
Model Number:
RGIS
Voltage:
24KV/27.5 KV/40.5KV
Supply Ability
Supply Ability:
50 Set/Sets per Month
Packaging & Delivery
Port
Ningbo

RGS SF6 Gas Insulated Metal-clad swi tchgear, RGS-G20 designed up to 40.5kV 3-phase 3 wire 50/60 Hz system.
The switchgear shall be rated up to 40.5kV and has horizontally or Vertically installed vacuum circuit breakers
The switchgear includes vacuum circuit breakers,meters, relays, etc.
The switchgear is certified by Xi'an High Voltage Institute.

++++Feature

Compactness,

Automation,

High Reliability and Safety,

Easy Expansion,

Simple Installation,

Economy.

++++Main technical parameter

 

Designation of type

 

RGIS

-G10

RGIS

-G2

RGIS

-G80

RGIS

-G90

Rated voltage

kV

24

40.5

40.

27.5

Maximum operating voltage

kV

24

40.5

40.5

27.5

Rated power frequency withstand voltage

kV

501)

95

95

95

Rated lightning impulse withstand voltage

kV

125

185

185

185

All voltage values apply for an

insulating gas pressure, absolute, 20

kPa

110

110

110

110

Rated frequency

Hz

50/60

50/60

50/60

50/60

Rated busbar current

A

up to 20001)

up to 12501)

up to 12501

up to 12501

Rated feeder current

A

630/

1250/

20001)

630/

12501)

630/

1250/

20001)

630/

1250/

20001)

Rated peak withstand current

kA

63

80

80

80

Rated short time current 4 seconds

kA

25

31.5

31.5

31.5

Rated short circuit breaking current of circuit breaker

kA

25

31.5

31.5

31.5

Rated short circuit making current of circuit breaker

kA

63

80

80

80

Rated operating sequence

 

O - 0.3s - CO - 3min - CO2)

Closing time

ms

75

60±5

60±5

60±5

Opening time

ms

60

40±5

40±5

40±5

Insulating gas

 

SF63)

SF63)

SF63)

SF63)

Rated filling pressure, absolute, 20

kPa

130

130

130

130

Minimum operating pressure, absolute, 20℃ kPa

kPa

120

120

120

120

Rated data: Auxiliary voltage

V

220DC 110 / 125DC4)

Degree of protection (IEC 60529, DIN VDE 0470) :

High voltage live parts

Low voltage compartment

 

 

IP 65

IP 4X5)

 

IP 65

IP 4X5)

 

IP 65

IP 4X5)

 

IP 65

IP 4X5)

Ambient temperature : 6)

Maximum value

Minimum value

 

 

+40

-15

 

+40

-15

 

+40

-15

 

+40

-15

Altitude for erection above sea level

mm

 

Dimensions :

Height

Depth

Width

 

mm

mm

mm

 

2300

1720

600/650

 

2300

1455

600/800/1000

 

2400(2600)7)

1760 600/800

 

2400(2600)7)

1760 600/800